Guangzhou Hiseer Air conditioning Co.Ltd
heat pump, hot water heater, heating, air conditioner, chiller, Manufacturer and Supplier - China
Air cooled chiller/heat pump (AW20)
Heating, cooling and domestic hot water
Adopt Siemens controller
Varied heat curve
SWEP plate heat exchanger
Galvanized sheet case
Stainless steel 443 case is optional
AIR TO WATER HEAT PUMP AW20/B
Heat output/Power consumption at 7/35℃ kW 21.7/5.7
Heat output/Power consumption at 7/45℃ kW 21.4/6.8
Heat output/Power consumption at 7/55℃ kW 20.8/8.4
Heat output/Power consumption at 2/35℃ kW 18.9/5.7
Heat output/Power consumption at 2/45℃ kW 18.5/6.8
Heat output/Power consumption at -7/35℃ kW 14.3/5.8
Heat output/Power consumption at -7/45℃ kW 14.2/6.9
Cool output/Power consumption at 35/7℃ KW 19.6/6.8
Starting current A 74
Soft-start relay
Power 380-415V/3PH/50Hz
Compressor HITACHI scroll
Condenser Swep Brazed plate heat exchanger
Nominal flow heating medium l/s 1.03
Internal pressure drop at nominal flow kPa 24
Air flow m3/h 6000
Nominal output fan W 440
Max outgoing heating medium temperature ℃ 55℃
Dimensions(HxWxD) mm 1050x1300x690
Pipe connector DN40
Weight kg 270
The above data is tested by EN14511