GCS Low-voltage Withdrawable Switchgear Cubicle (large number) | | | Product Feature | GENERAL
It is suitable for power distribution system of power plants,oil and chemical industry,metallurgy industry,textile industry and high buildings especially in the place where requires for high automation and connection to computers such as large power plants and petro-chemi-cal industry.it adapts to 3-phase system with frequency 50(60)Hz,rated voltage 380V (400),(660), rated current 4000A max,and is used for low voltage distribution equipment of power supply system,motor contol center and reactive power compensation.
STRUCTURE
1. The main structure is made of shaped steel of type 8MF with two mounting holes(m=20mm,100mm,and diamet-er-9.2mm) on both sides.It is flexible and convenient to assemble.
2. The function units are diveded into three compartment:function compartment,busbar compartment,busbar compartment and cable conpartment,each has independent function.
3. The horizontal busbar arrange in parallel at the back of cubicle to strength their resistance to electeic power,which is the basic measure to make main curcuit have high intensity of short circuit.
4. The design of disconnected unit for cable makes it convenient for cable's use.
| | | | Product Specifications | MAIN TECHNICAL PARAMETERS
Rated voltage of main circuit(V) AC 380(400a??660)
AC380(400a??660)
Rated voltage of auxiliary circuit(V) AC220a??380(400)
DC110a??220
AC 220a??380(400)
DC 110a??220
Rated frequency(Hz) 50(60)
Rated insulation voltage(V) 660(1000)
Rated current(A) Horizontal busbar a??4000
Vertical busbar 1000
Rated short time withstand current of busbar 50a??80
Rated peak withstand current of busbar 105a??176
(V/min) Rated power frequency with and voltage(1min) Main curcuit 2500
Auxlilary curcuit 1760
Busbar 3-phase and 4-wire A.B.C PEN
3-phase and 5-wire A.B.C PE.N
Degrees of protection IP3L0.IP4L0
Dimensions 2000x(600 800 1000)x600(800 1000)
NOTES FOR ORDERING
supply the following documents:
a. All the types of the switchgear including the main circuit scheme number and the supplementary circuit scheme number.
b. The assembly sequence diagrams of the main circuit system.
c. The electric principle diagrams of the auxiliary circuit.
d. The inner cubicle components list.
e. The data of voltage,current,time in circuit.
f. The special requirements not under the normal service condition.
| | | |
| |